SOUND CONTROL ASSEMBLY : PGD-33-497-24
ASSEMBLY COMPONENTS
            - 
                            
Acoustical
STC 58
NOAL 22-0917
 - 
                            
Fire
2 hrs.
U425
 - 
                            
Dimensions
Thickness: 6-1/8
Approx. Weight: 10.6 lb/ft²
 - 
                            
Bearing
Limited Load Bearing
 
ASSEMBLY DETAILS
- 1-5/8” Type S-12 screws spaced 12” o.c.
 - Face layer: 5/8” type X (FLAME CURB®, MOLD CURB® Plus, ABUSE CURB®, PABCO® Impact Resistant, PABCO® Glass Interior, PABCO® Glass Sheathing or PABCO® Gypsum Sheathing) gypsum panel applied vertically.
 - 1-1/4” Type S-12 screws spaced 12” o.c. (for fire, minimum 1” S-12 screws).
 - Base layer: 5/8” QuietRock® ES or QuietRock® ES MR type X gypsum panel applied vertically.
 - 3-5/8” 33 mil steel studs, 24” o.c.
 - 3-1/2”, R-13 glass fiber insulation friction fit into stud cavity.
 - Base layer: 5/8” QuietRock® ES or QuietRock® ES MR type X gypsum panel applied vertically.
 - 1-1/4” Type S-12 screws spaced 12” o.c. (for fire, minimum 1” S-12 screws).
 - Face layer: 5/8” type X (FLAME CURB®, MOLD CURB® Plus, ABUSE CURB®, PABCO® Impact Resistant, PABCO® Glass Interior, PABCO® Glass Sheathing or PABCO® Gypsum Sheathing) gypsum panel applied vertically.
 - 1-5/8” Type S screws spaced 12” o.c.